Ademco/Resideo - TH3110D1008 - Backlit Display. 1 Heat/1 Cool. Dual Pow Backlit Display. 1 Heat/1 Cool. Dual Power - (Battery And Hardwire.) English And Spanish Packaging And Installation Instructions. Premier White In Color.

Overview

The PRO series provides non-programmable thermostats for 24 Vac conventional and heat pump systems or 750 mV heating systems.

Features

  • Non-programmable digital thermostat.
  • Backlit digital display - both current and set temperatures are easy to read in various lighting conditions.
  • Precise comfort control ( 1ªF) - maintains consistent comfort to the highest level of accuracy.
  • Basic operation - easy-to-use slide switches allow you to select the heat or cool mode, and operate the fan.
  • 5-year limited warranty.

 

Customer Rating: Not Rated Yet
Quick Order Number: 195
Manufacturer: Ademco/Resideo
Part Number: TH3110D1008/U
Weight: 0.75 lbs
Stocked Item*: No
Quantity Available*: 0
Price: $59.59
Quantity:

* If an order is placed where the item is a "Non-Stocked Item" or the quantity ordered is more than the quantity available, all items in stock will be shipped and the remainder of the items will be shipped as soon as we get the "backordered" items in.

 

Product Specifications

 

Product Specifications

Application
1 Heat/1 Cool Conventional Systems and Heat Pumps with No Auxiliary Heat
Dimensions (in.)
3 13/16 in. High X 5 3/8 in. Wide X 1 1/4 in. Deep
Dimensions (mm)
97 mm High X 137 mm Wide X 32 mm Deep
Mounting
Horizontal
Electrical Ratings
20 to 30 Vac or 750 mV
Frequency
50 Hz; 60 Hz
Stages
1 Heat/1 Cool
Operating Humidity Range (% RH)
5 to 90% RH, non-condensing
Supply Voltage
20 to 30 Vac; 750 mV
Switch Positions (System)
HEAT-OFF-COOL
Switch Positions (Fan)
AUTO-ON
Sensor Element
Thermistor
Accuracy (F)
±1 F
Accuracy (C)
± 0.5 C
Color
Premier White®
Switch Type
Relay
Power Method
Dual Powered: Battery or Hardwire
Terminal Designations
R, Rc, W, Y, G, O, B, C
Display Size
1.32 sq in.
Changeover
Manual
Setting Temperature Range (F)
Heat: 40 F to 90 F; Cool: 50 F to 99 F
Setting Temperature Range (C)
Heat: 4.5 C to 32 C; Cool: 10 C to 37 C
Cycles per Hour
Heating 1-12 CPH; Cooling 1-6 CPH
Cool Current
0.02 A to 1.0 A running
Heat Current
0.02 A to 1.0 A running

 